KFD2-VR4-EX1.26长安十二时辰推荐安全栅General specifications Signal type Analog input Functional safety related parameters Safety Integrity Level (SIL) SIL 2 Supply Connection Power Rail or terminals 11 , 12- Rated voltage 19 ... 30 V DC Ripple within the supply tolerance Power dissipation ≤ 1.2 W Power consumption ≤ 1.6 W Input Connection side field side Connection terminals 4 (common), 1, 3 and 5 (supply -), 2 and 6 (signal -) Input resistance 10 kΩ terminals 4 (common), 6-/2- Output rated operating current terminals 4 (common), 5-: > 10 mA at -21 V or > 20 mA at -18 V
terminals 4 (common), 1-: 5.3 mA ?0.4 mA at -10 V
terminals 4 (common), 3-: 3.6 mA ?0.7 mA at -10 V, 20 ?C (68 ?F)Transmission range -20 ... 0 V Output Connection side control side Connection terminals 7-, 8 Load ≥ 9 kΩ (3-wire sensor), ≥ 2 kΩ (2-wire sensor) Voltage -20 ... 0 V Output resistance 24 Ω typ., 27 Ω maximum
Since this is much less than the end-to-end resistance of a zener barrier, it may be necessary to specify a monitor intended for use without a barrier. Please follow the advice of the monitor manufacturer.Transfer characteristics Cut-off frequency 10 kHz (-0,1 dB)
20 kHz (-1 dB)Deviation DC transfer error (with 10 kΩ load) < 10mV After calibration additional error with AC superimposed is ?5 mV at 20 ?C (68 ?F) at any point within the span, provided that the alternating component of the input voltage is not excessive, e. g.
- square waves (0 ... 20 kHz): 5 Vpp
- sine waves (0 ... 20 kHz): the full span of 20 Vpp (= 100 g peak acceleration at 100 mV/g) is acceptable.Influence of ambient temperature (< 100 ppm of span)/K at any point within the span Time delay relative to input 7.1 ?0.3 ?s Ripple in 200 kHz bandwidth < 20 mVrms
in 20 kHz bandwidth < 3 mVrmsGalvanic isolation Output/power supply functional insulation, rated insulation voltage 50 V AC Indicators/settings Display elements LED Labeling space for labeling at the front Directive conformity Electromagnetic compatibility Directive 2014/30/EU EN 61326-1:2013 (industrial locations) Conformity Electromagnetic compatibility NE 21:2017
EN 61326-3-2:2018Degree of protection IEC 60529 Protection against electrical shock UL 61010-1 Ambient conditions Ambient temperature -20 ... 60 ?C (-4 ... 140 ?F) Mechanical specifications Degree of protection IP20 Connection screw terminals Mass approx. 125 g Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001 Data for application in connection with hazardous areas EU-type examination certificate BAS 02 ATEX 7206 Marking
II (1)GD, [Ex ia Ga] IIC, [Ex ia Da] IIIC, (-20 ?C ≤ Tamb ≤ 60 ?C) [circuit(s) in zone 0/1/2]Input Ex ia Ga, Ex ia Da Voltage -26.4 V Current 90 mA Power 570 mW Supply Maximum safe voltage 253 V (Attention! The rated voltage can be lower.) Output Maximum safe voltage 253 V (Attention! The rated voltage is lower.) EU-type examination certificate DMT 01 ATEX E 133 Marking
I (M1) [Ex ia] ICertificate T?V 99 ATEX 1499 X Marking
II 3G Ex nA II T4 [device in zone 2]Galvanic isolation Input/Output safe galvanic isolation acc. to IEC 60079-11, voltage peak value 375 V Input/power supply safe galvanic isolation acc. to IEC 60079-11, voltage peak value 375 V Directive conformity Directive 2014/34/EU EN 60079-0:2012 A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000 International approvals UL approval Control drawing 116-0316 (cULus) IECEx approval IECEx certificate IECEx BAS 05.0078
IECEx BAS 10.0085XIECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Ex nA II T4 GcGeneral information Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. Accessories Optional accessories - power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)