| 价格 | 111.00元 |
|---|---|
| 品牌 | 倍加福 |
| 区域 | 全国 |
| 来源 | 重庆派欧工业自动化控制设备有限公司 |
详情描述:
倍加福现货KFD2-UT2-2信号转换信号调节器产品阐述 Current output 0/4 mA ... 20 mA General specifications Signal type Analog input Functional safety related parameters Safety Integrity Level (SIL) SIL 2 Supply Connection terminals 14 , 15- or power feed module/Power Rail Rated voltage 20 ... 30 V DC Ripple within the supply tolerance Power dissipation/power consumption ≤ 1.53 W / 1.53 W Interface Programming interface programming socket Input Connection side field side Connection terminals 1, 2, 3; 4, 5, 6 RTD type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760)Measuring current approx. 200 ?A with RTD Types of measuring 2-, 3-wire connection Lead resistance max. 50 Ω per line Measurement loop monitoring sensor breakage, sensor short-circuit Thermocouples type B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001)Cold junction compensation external and internal Measurement loop monitoring sensor breakage Potentiometer 0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection) Voltage selectable within the range -100 ... 100 mV Input resistance ≥ 1 MΩ (-100 ... 100 mV) Output Connection side control side Connection output I: terminal 7: source (-), sink ( ), terminal 8: source ( ), terminal 9: sink(-)
output II: terminal 10: source (-), sink ( ), terminal 11: source ( ), terminal 12: sink(-)Output I, II Analog current output Current range 0 ... 20 mA or 4 ... 20 mA Fault signal downscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43) Source load 0 ... 550 Ω
open-circuit voltage ≤ 18 VSink Voltage across terminals 5 ... 30 V. If the current is supplied from a source > 16.5 V,
series resistance of ≥ (V - 16.5)/0.0215 Ω is needed, where V is the source voltage.
The maximum value of the resistance is (V - 5)/0.0215 Ω.Transfer characteristics Deviation After calibration Pt100: ? (0.06 % of measurement value in K 0.1 % of span 0.1 K (4-wire connection))
thermocouple: ? (0.05 % of measurement value in ?C 0.1 % of span 1 K (1.2 K for types R and S))
this includes ? 0.8 K error of the cold junction compensation
mV: ? (50 ?V 0.1 % of span)
potentiometer: ? (0.05 % of full scale 0.1 % of span, (excludes errors due to lead resistance))Influence of ambient temperature deviation of CJC included:
Pt100: ? (0.0015 % of measurement value in K 0.006 % of span)/K ΔTamb*)
thermocouple: ? (0.02 K 0.005 % of measurement value in ?C 0.006 % of span)/K ΔTamb*)
mV: ? (0.01 % of measurement value 0.006 % of span)/K ΔTamb*)
potentiometer: ? 0.006 % of span/K ΔTamb*)
*) ΔTamb = ambient temperature change referenced to 23 ?C (296 K)Influence of supply voltage < 0.01 % of span Influence of load ≤ 0.001 % of output value per 100 Ω Reaction time worst case value (sensor breakage and/or sensor short circuit detection enabled)
mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 sGalvanic isolation Input/Other circuits basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff Output/supply, programming input functional insulation, rated insulation voltage 50 V AC
There is no electrical isolation between the programming input and the supply.
The programming cable provides galvanic isolation so that ground loops are avoided.Indicators/settings Display elements LEDs Configuration via PACTware Labeling space for labeling at the front Directive conformity Electromagnetic compatibility Directive 2014/30/EU EN 61326-1:2013 (industrial locations) Conformity Electromagnetic compatibility NE 21:2006 Degree of protection IEC 60529:2001 Ambient conditions Ambient temperature -20 ... 60 ?C (-4 ... 140 ?F) Mechanical specifications Degree of protection IP20 Connection screw terminals Mass approx. 130 g Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001 General information Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.